Daisy
DAISY is Marvon’s fire collar designed and developed to ensure El 240 fire resistance of penetration seals on wall and floor according to EN 1366-3.
DAISY is made of a red coated steel shell that can be opened to allow the accommodation even on already installed pipes and it has a hanger with a latch mechanism. The back flange with attachment buttonholes ensures a simple setting and a fast installation. The resistance and insulation El 240 is guaranteed by the presence of two different types of intumescent graphite based reactive material (TECNOFLAME + EVA) and of special closure metal elements (petals).
The ethylene vinyl acetate (EVA) seal expands fast at low temperatures whereas the seal TECNOFLAME expands later so that it ensures high performance in time. While expanding, the intumescent seals act on the closure elements (petals) bringing them towards the position of fire exposure, creating an additional barrier.
Application field
The fire collar DAISY can be used on rigid wall (masonry, concrete or aerated concrete) and on rigid floor (concrete or aerated concrete).
It has an EI 240 fire resistance classified according to EN 13501-2 for:
- Combustible pipes (PVC-U, PVC-C, PE, LDPE, MDPE, HDPE, ABS, SAN+PVC, PP)
- Combustible soundproof pipes (e.g. Valsir Triplus®, Valsir Silere®, Valsir PP3, Valsir Blackfire®)


Technical data
Fire resistance |
EI 240 |
Fire reaction |
NPD |
Diameters |
Ø 32 - 160 |
Collar’s height |
49,5 - 89,5 mm |
Shell |
Carbon-coated steel (1 mm thickness) with a lever hook and slotted flange |
Intumescent material |
Two different types of intumescent seal:
|
Colou |
Red |
Storage |
Unlimited (in normal conditions) |
Operating principle
In the event of fire, the intumescent material contained in the collar expands forming a “plug” thus cutting off the fire and preventing the passage of gas and fumes.
The special closure elements (reinforcement wings) increase the reactivity and efficiency of the system by completely squeezing the plastic pipe during the melting phase.



Phase 1
In the first phase of the fire, the plastic pipe melts and the intumescent elements expand. The first, more reactive, acts immediately, the second, which expands at a higher temperature, gives higher performance over time.
Phase 2
In the minutes that follow, the intumescent elements occupy the entire section that is left free after the plastic pipe has melted. The intumescent elements act on the closure elements (reinforcement wings) bringing them toward the position of exposure to the fire.
Phase 3
The intumescent elements close off the hole entirely in a sufficiently brief time so that the fire does not spread outside the compartmentalization. The closure elements (reinforcement wings) in this phase are completely oriented and, as well as acting as a “container” for the expanded intumescent material, create another metal barrier against the fire.
Installation phases

Make a hole in the wall or ceiling and insert the pipe.

Prepare the sealing mortar required to completely fill the space between the pipe and the hole.

Seal the gap with the sealing mortar

Position the collar against the wall or ceiling and trace the position of the holes.

Drill the holes for the wall plugs.

Mount the Daisy collar onto the pipe and secure it using the lever closure.

Insert the plugs in the holes.

Tighten the nuts.

The Daisy collar has been installed.
Standard rules and certifications
- Test Standard: EN 1366-3
- Fire Classification Standard: EN 13501-2
-
Classification Reports:
- CSI1862FR – wall
- CSI1915FR - floor
- CSI1917FR - wall
Tecnoboard
TECNOBOARD is Marvon’s fire board designed and developed to ensure fire resistance up to El 240 of penetration seals on wall and floor according to EN 1366-3.
TECNOBOARD is composed of a mineral wool board coated on both sides with a white intumescent paint.
In contact with fire the paint reacts and expand, thereby preventing the passage of flame and acting as a thermal insulation.
Application field
TECNOBOARD can be used on flexible wall (gypsum), on rigid wall (masonry, concrete and aerated concrete)
and on rigid floor (concrete or aerated concrete).
It has a fire resistance up to El 240 classified according to EN 13501-2 for:
- Combustible pipes (PVC-U, PVC-C, PE, LDPE, MDPE, HDPE, ABS, SAN+PVC, PP)
- Combustible soundproof pipes (e.g. Valsir Triplus®, Valsir Silere®, Valsir PP3, Valsir Blackfire®)
- Insulated and non-insulated multilayer pipes
- Insulated and non-insulated incombustible pipes (copper or steel)
- Single or bundled electrical cables
- Cable trays and corrugated pipes
- Empty holes
N.B. The board is used in case of large crossing and penetration of mixed services. Seal any remaining gap with TECNO-S 240 sealant.
Use TECNOWRAP intumescent seal in the solutions provided by ETA.
Technical data
Fire resistance |
Up to El 240 |
Fire reaction |
Performance not assessed |
Dimensions |
1200x600 mm |
Board thickness |
60 mm |
Weight |
7,6 kg/pcs |
Coating |
White intumescent paint on both sides of board |
Density |
|
Thermal conductibility |
0,038 W/mK |
Installation temperature |
5 - 50°C |
Temperature range |
-30 - +80°C |
Content, emission and/ |
IA1 |
Storage |
Unlimited (in normal conditions) |
Working life |
25 years |
TVOC |
0,2 mg/m2h |
Durability |
Y1: intended for use at temperatures below 0°C with exposure to UV but no exposure to rain. Includes lower classes Y2, Z1, Z2. |
AVCP system |
1 |
Standard rules and certifications
- Test Standard: EN 1366-3
- Fire Classification Standard: EN 13501-2
- European Assessment Document: EAD 350454-00-1104
- European Technical Assessment: ETA 22/0429.
Tecnowrap
TECNOWRAP is Marvon’s intumescent seal designed and developed to ensure fire resistance up to El 240 of penetration seals on wall and floor according to EN 1366-3.
TECNOWRAP is composed of an intumescent graphite based reactive material that in case of fire reacts sealing the crossing.
Application field
TECNOWRAP can be used on: flexible wall (gypsum), rigid wall (masonry, concrete and aerated concrete), timber wall, rigid floor (concrete or aerated concrete), timber floor.
It has a fire resistance up to El 240 classified according to EN 13501-2 for:
- Combustible pipes (PVC-U, PVC-C, PE, LDPE, MDPE, HDPE, ABS, SAN+PVC, PP)
- Combustible soundproof pipes (Valsir Triplus®, Valsir Silere®, Valsir PP3, Valsir Blackfire®)
- Multilayer pipes.
- Incombustible pipes.
N.B. The annular space around TECNOWRAP is sealed with TECNOBOARD.
Technical data
Fire resistance |
Up to El 240 |
Fire reaction |
Performance not assessed |
Dimensions |
50x1,8 mm |
Roll length |
25 m |
Weight |
3,2 kg/pz |
Intumescent material |
|
Colour |
Anthracite grey |
Content, emission and/or release of dangerous substances |
IA1, S/W3 |
Storage |
Unlimited (in normal conditions) |
Working life |
25 years |
Durability |
X: use with exposure to atmospheric agents |
AVCP system |
1 |
Standard rules and certifications
- Test Standard: EN 1366-3.
- Fire Classification Standard: EN 13501-2.
- European Assessment Document: EAD 350454-00-1104.
- European Technical Assessment: ETA 22/0429.
Tecnobag
TECNOBAG is Marvon’s fire bag designed and developed to ensure fire resistance up to El 120 of penetration seals on wall and floor according to EN 1366-3.
TECNOBAG consists of a special mixture of inert material, intumescent material and insulating material inside a fiberglass housing. At 180°C, the expansion process begins, hence insulating the penetration seals.
Application field
TECNOBAG can be used on flexible wall (plasterboard), on rigid wall (masonry, concrete or aerated concrete) and on rigid floor (concrete or aerated concrete).
It has a fire resistance up to El 120 classified according to EN 13501-2 for:
- Cable trays
Technical data
Fire resistance |
Up to EI 120 |
Fire reaction |
B-s1, d0 |
Dimensions |
100x120x25 - 200x120x30 |
Weight |
300 g/pz +/- 30 g - 600 g/pz +/- 60 g |
Storage |
Unlimited (under normal conditions) |
Working life |
10 years |
Durability |
Y2:intended for use at temperatures below 0°C, but without exposure to UV and rain. |
AVCP system |
1 |
Standard rules and certifications
- Test Standard: EN 1366-3
- Fire Classification Standard: EN 13501-2
- European Assessment Document: ETAG 026-2
- European Technical Assessment: ETA 16/0733
Tecnobrick
TECNOBRICK is Marvon’s polyurethane sponge intumescent brick designed and developed to ensure fire resistance up to EI 180 of penetration seals on wall and floor according to EN 1366-3.
TECNOBRICK is an easily shaped spongy product suitable to seal holes in different geometries.
When exposed to fire, it expands at 200°C further increasing its volume thanks to the presence of graphite.
Application field
TECNOBRICK can be used on flexible wall (plasterboard), on rigid wall (masonry, concrete or aerated concrete
and on rigid floor (concrete or aerated concrete).
It has a fire resistance up to EI 180 to classified according to EN 13501-2 for:
- Combustible pipes (PVC-U, PVC-C)
- Insulated multilayer pipes
- Insulated incombustible pipes (copper or steel)
- Cable trays and corrugated pipes
- Empty holes
- Ventilation ducts
N.B. The brick is used in case of large crossing and penetration of mixed services. Seal any remaining gap with TECNOGRAPHIT foam.
Technical data
Fire resistance |
Up to EI 180 |
Fire reaction |
Performance not assessed |
Dimensions |
150x150x50 |
Weight |
220 g/pz |
Density |
240 ±10% kg/m3 |
Thermal conductivity |
0,062 W/mK |
Application temperature |
5 - 35°C |
Colour |
Dark grey |
Storage |
Unlimited (under normal conditions) |
Standard rules and certifications
- Fire Classification Standard: EN 13501-2
-
Classification Reports:
- I.G. 365276/4000FR - floor - penetration seal P, Q
- I.G. 361718/3981FR - wall - penetration seal A, D, G
- I.G. 367546/4008FR - wall - infill E
- European Technical Assessment: ETA 21/0580.