Daisy

DAISY is Marvon’s fire collar designed and developed to ensure El 240 fire resistance of penetration seals on wall and floor according to EN 1366-3.

DAISY is made of a red coated steel shell that can be opened to allow the accommodation even on already installed pipes and it has a hanger with a latch mechanism. The back flange with attachment buttonholes ensures a simple setting and a fast installation. The resistance and insulation El 240 is guaranteed by the presence of two different types of intumescent graphite based reactive material (TECNOFLAME + EVA) and of special closure metal elements (petals).

The ethylene vinyl acetate (EVA) seal expands fast at low temperatures whereas the seal TECNOFLAME expands later so that it ensures high performance in time. While expanding, the intumescent seals act on the closure elements (petals) bringing them towards the position of fire exposure, creating an additional barrier.

Application field

The fire collar DAISY can be used on rigid wall (masonry, concrete or aerated concrete) and on rigid floor (concrete or aerated concrete).

It has an EI 240 fire resistance classified according to EN 13501-2 for:

  • Combustible pipes (PVC-U, PVC-C, PE, LDPE, MDPE, HDPE, ABS, SAN+PVC, PP)
  • Combustible soundproof pipes (e.g. Valsir Triplus®, Valsir Silere®, Valsir PP3, Valsir Blackfire®)
 
daisy montaggio semplificato
daisy montaggio semplificato
 

Technical data

Fire resistance

EI 240

Fire reaction

NPD

Diameters

Ø 32 - 160

Collar’s height

49,5 - 89,5 mm

Shell

Carbon-coated steel (1 mm thickness) with a lever hook and slotted flange

Intumescent material

Two different types of intumescent seal:

  • TECNOFLAME, PVC and graphite based
    • Expansion ratio 1:5.5 / 9.5
    • Density 1,000 - 1,400 kg/m3
    • Minimum expansion temperature 180°C
  • EVA, ethylene vinyl acetate graphite based
    • Expansion ratio 1:30
    • Density 1,000 kg/m3
    • Minimum expansion temperature 140°C

Colou

Red

Storage

Unlimited (in normal conditions)

Operating principle

In the event of fire, the intumescent material contained in the collar expands forming a “plug” thus cutting off the fire and preventing the passage of gas and fumes.

The special closure elements (reinforcement wings) increase the reactivity and efficiency of the system by completely squeezing the plastic pipe during the melting phase.

Collare tagliafuoco Marvon Daisy: fase 1
Collare tagliafuoco Marvon Daisy: fase 2
Collare tagliafuoco Marvon Daisy: fase 3

Phase 1

In the first phase of the fire, the plastic pipe melts and the intumescent elements expand. The first, more reactive, acts immediately, the second, which expands at a higher temperature, gives higher performance over time.

Phase 2

In the minutes that follow, the intumescent elements occupy the entire section that is left free after the plastic pipe has melted. The intumescent elements act on the closure elements (reinforcement wings) bringing them toward the position of exposure to the fire.

Phase 3

The intumescent elements close off the hole entirely in a sufficiently brief time so that the fire does not spread outside the compartmentalization. The closure elements (reinforcement wings) in this phase are completely oriented and, as well as acting as a “container” for the expanded intumescent material, create another metal barrier against the fire.

Installation phases

Montaggio collarwings: fase 01

Make a hole in the wall or ceiling and insert the pipe.

Montaggio collarwings: fase 02

Prepare the sealing mortar required to completely fill the space between the pipe and the hole.

Montaggio collarwings: fase 03

Seal the gap with the sealing mortar

Montaggio collarwings: fase 04

Position the collar against the wall or ceiling and trace the position of the holes.

Montaggio collarwings: fase 05

Drill the holes for the wall plugs.

Montaggio collarwings: fase 06

Mount the Daisy collar onto the pipe and secure it using the lever closure.

Montaggio collarwings: fase 07

Insert the plugs in the holes.

Montaggio collarwings: fase 08

Tighten the nuts.

Montaggio collarwings: fase 09

The Daisy collar has been installed.

Standard rules and certifications

  • Test Standard: EN 1366-3
  • Fire Classification Standard: EN 13501-2
  • Classification Reports:
    • CSI1862FR – wall
    • CSI1915FR - floor
    • CSI1917FR - wall

Tecnoboard

TECNOBOARD is Marvon’s fire board designed and developed to ensure fire resistance up to El 240 of penetration seals on wall and floor according to EN 1366-3.

TECNOBOARD is composed of a mineral wool board coated on both sides with a white intumescent paint.
In contact with fire the paint reacts and expand, thereby preventing the passage of flame and acting as a thermal insulation.

Application field

TECNOBOARD can be used on flexible wall (gypsum), on rigid wall (masonry, concrete and aerated concrete)
and on rigid floor (concrete or aerated concrete).

It has a fire resistance up to El 240 classified according to EN 13501-2 for:

  • Combustible pipes (PVC-U, PVC-C, PE, LDPE, MDPE, HDPE, ABS, SAN+PVC, PP)
  • Combustible soundproof pipes (e.g. Valsir Triplus®, Valsir Silere®, Valsir PP3, Valsir Blackfire®)
  • Insulated and non-insulated multilayer pipes
  • Insulated and non-insulated incombustible pipes (copper or steel)
  • Single or bundled electrical cables
  • Cable trays and corrugated pipes
  • Empty holes

N.B. The board is used in case of large crossing and penetration of mixed services. Seal any remaining gap with TECNO-S 240 sealant.
Use TECNOWRAP intumescent seal in the solutions provided by ETA.

Technical data

Fire resistance

Up to El 240

Fire reaction

Performance not assessed

Dimensions

1200x600 mm

Board thickness

60 mm

Weight

7,6 kg/pcs

Coating

White intumescent paint on both sides of board

Density

  • Board 160 kg/m3
  • Coating 1350 kg/m3

Thermal conductibility

0,038 W/mK

Installation temperature

5 - 50°C

Temperature range

-30 - +80°C

Content, emission and/
or release of dangerous
substances

IA1

Storage

Unlimited (in normal conditions)

Working life

25 years

TVOC

0,2 mg/m2h

Durability

Y1: intended for use at temperatures below 0°C with exposure to UV but no exposure to rain. Includes lower classes Y2, Z1, Z2.

AVCP system

1

Standard rules and certifications

  • Test Standard: EN 1366-3
  • Fire Classification Standard: EN 13501-2
  • European Assessment Document: EAD 350454-00-1104
  • European Technical Assessment: ETA 22/0429.

 

Tecnowrap

TECNOWRAP is Marvon’s intumescent seal designed and developed to ensure fire resistance up to El 240 of penetration seals on wall and floor according to EN 1366-3.

TECNOWRAP is composed of an intumescent graphite based reactive material that in case of fire reacts sealing the crossing.

Application field

TECNOWRAP can be used on: flexible wall (gypsum), rigid wall (masonry, concrete and aerated concrete), timber wall, rigid floor (concrete or aerated concrete), timber floor.
 

It has a fire resistance up to El 240 classified according to EN 13501-2 for:

  • Combustible pipes (PVC-U, PVC-C, PE, LDPE, MDPE, HDPE, ABS, SAN+PVC, PP)
  • Combustible soundproof pipes (Valsir Triplus®, Valsir Silere®, Valsir PP3, Valsir Blackfire®)
  • Multilayer pipes.
  • Incombustible pipes.

N.B. The annular space around TECNOWRAP is sealed with TECNOBOARD.

Technical data

Fire resistance

Up to El 240

Fire reaction

Performance not assessed

Dimensions

50x1,8 mm

Roll length

25 m

Weight

3,2 kg/pz

Intumescent material

  • Graphite based
  • Minimum expansion temperature 105°C
  • Average expansion time less than 10 minutes
  • Expansion ratio 1:28
  • Expansion pressure 55 N
  • Graphite weight 1.3 kg/m2 per mm thickness
  • Graphite density 1,300 kg/m3
  • With biadhesive

Colour

Anthracite grey

Content, emission and/or release of dangerous substances

IA1, S/W3

Storage

Unlimited (in normal conditions)

Working life

25 years

Durability

X: use with exposure to atmospheric agents

AVCP system

1

Standard rules and certifications

  • Test Standard: EN 1366-3.
  • Fire Classification Standard: EN 13501-2.
  • European Assessment Document: EAD 350454-00-1104.
  • European Technical Assessment: ETA 22/0429.

Tecnobag

TECNOBAG is Marvon’s fire bag designed and developed to ensure fire resistance up to El 120 of penetration seals on wall and floor according to EN 1366-3.

TECNOBAG consists of a special mixture of inert material, intumescent material and insulating material inside a fiberglass housing. At 180°C, the expansion process begins, hence insulating the penetration seals.

Application field

TECNOBAG can be used on flexible wall (plasterboard), on rigid wall (masonry, concrete or aerated concrete) and on rigid floor (concrete or aerated concrete).

It has a fire resistance up to El 120 classified according to EN 13501-2 for:

  • Cable trays

Technical data

Fire resistance

Up to EI 120

Fire reaction

B-s1, d0

Dimensions

100x120x25 - 200x120x30

Weight

300 g/pz +/- 30 g - 600 g/pz +/- 60 g

Storage

Unlimited (under normal conditions)

Working life

10 years

Durability

Y2:intended for use at temperatures below 0°C, but without exposure to UV and rain.
Includes lower classes Z1 and Z2.

AVCP system

1

Standard rules and certifications

  • Test Standard: EN 1366-3
  • Fire Classification Standard: EN 13501-2
  • European Assessment Document: ETAG 026-2
  • European Technical Assessment: ETA 16/0733

Tecnobrick

TECNOBRICK is Marvon’s polyurethane sponge intumescent brick designed and developed to ensure fire resistance up to EI 180 of penetration seals on wall and floor according to EN 1366-3.

TECNOBRICK is an easily shaped spongy product suitable to seal holes in different geometries.

When exposed to fire, it expands at 200°C further increasing its volume thanks to the presence of graphite.

Application field

TECNOBRICK can be used on flexible wall (plasterboard), on rigid wall (masonry, concrete or aerated concrete
and on rigid floor (concrete or aerated concrete).

It has a fire resistance up to EI 180 to classified according to EN 13501-2 for:

  • Combustible pipes (PVC-U, PVC-C)
  • Insulated multilayer pipes
  • Insulated incombustible pipes (copper or steel)
  • Cable trays and corrugated pipes
  • Empty holes
  • Ventilation ducts

N.B. The brick is used in case of large crossing and penetration of mixed services. Seal any remaining gap with TECNOGRAPHIT foam.

Technical data

Fire resistance

Up to EI 180

Fire reaction

Performance not assessed

Dimensions

150x150x50

Weight

220 g/pz

Density

240 ±10% kg/m3

Thermal conductivity

0,062 W/mK

Application temperature

5 - 35°C

Colour

Dark grey

Storage

Unlimited (under normal conditions)

Standard rules and certifications

  • Fire Classification Standard: EN 13501-2
  • Classification Reports:
    • I.G. 365276/4000FR - floor - penetration seal P, Q
    • I.G. 361718/3981FR - wall - penetration seal A, D, G
    • I.G. 367546/4008FR - wall - infill E
  • European Technical Assessment: ETA 21/0580.